Burner Control Siemens LAL 2.14 – Burner controls LAL has a designed lifetime* of 250,000 burner startup cycles which,
under normal operating conditions in heating mode, correspond to approx. 10 years of usage (starting from the production date given on the type field). This lifetime is based on the endurance tests in the standard EN 298. A summary of the conditions has been published by the European Control Manufacturers Association (Afecor (www.afecor.org). The designed lifetime is based on use of the burner controls according to the manufacturer’s Data Sheet. After reaching the designed lifetime in terms of the number of burner startup cycles, or the respective time of usage, the burner control is to be replaced by authorized personnel.

Oil burner controls
- For oil atomizing burners of medium to large capacity
- For multistage or modulating burners in intermittent operation
- With or without air pressure supervision for checked air damper control
Flame supervision
– with photoresistive detector QRB1/QRB3
– or blue-flame detector QRC1
– or photocell detector RAR9