Pressure Switch


Pressure Switch Sauter
Type : DSB 146 F001
For regulating and monitoring pressure in liquids, gases and vapours, according to VdTÜV pressure
information sheet 100. Especially suitable for applications in compact installations, for pipe mounting
or wall mounting.
Minimum pressure limiter DSL:
When the pressure drops below the lower change-over point (adjustable setpoint Xs), the pressure
limiter locks mechanically and switches the contact from 1-3 to 1-2.
When the pressure rises by the min. pressure increase Xsd above the lower change-over point, the
contact can be switched back from 1-2 to 1-3 by pulling the reset button using a screwdriver.